BEC Automation › Products › Altus Nexto Jet I/O System
NJ1001
24 Vdc 16 DI Module
Key specifications
- 24 Vdc 16 DI Module NJ1001 Nexto Series
- In this context, Nexto Jet is a selection of I/O modules that uses the existing CPUs and modules from Nexto Series to provide the best solution for applications in verticals like infrastructure, building, water, wastewater, food, machines and
- several OEM projects. Nexto Jet is ideal for systems with no hot-swapping and conformal coating requirements. Finally, the module NJ1001 is a module that offers 16 isolated inputs of source/sink type for general use and it is a module
- Code Description NJ1001 24 Vdc 16 DI Module
- Backplane rack occupation 1 slot Input type Sink or source type 1
- Number of inputs 16 digital inputs Input voltage
- Status and diagnostic indication Display, web pages and CPU’s internal memory Hot swap capability No
- Standards IEC 61131-2
- UL Listed (file E473496) Module dimensions (W x H x D) 17.90 x 113.00 x 117.46 mm
- Input type: NJ1001’s inputs are divided in four input groups: 00 to 03, 04 to 07, 10 to 13 and 14 to 17. Each group can be used as source input as well as sink inputs independently of the type used in the other groups. To use an input group as
- Altus S. A. 4 Input filter: The usage of digital input filter is indicated for environments susceptible to high electromagnetic interference
- levels to the defined in the standard IEC 61131-2 or due to special features of used sensor. Installation
- 1 – Typical usage of source digital inputs, C2 is the +24 Vdc common to input group I04 to I07. 2 – Typical usage of sink digital inputs, C3 is the 0 Vdc common to input group I10 to I13.
- The mechanical and electrical mounting and the connector insertion and removing for single hardware width I/O modules are described at Nexto Series User Manual – MU214600.
- ATTENTION: The CPUs, racks and the PROFIBUS remote head of Nexto Series support the use of Nexto
- Jet Modules. The Nexto Jet is formed by I/Os modules and when used in configuration with CPUs or PROFIBUS remote head of Nexto Series, no other I/O type of Nexto Series can be
- variables delivered by NJ1001. The process data of the module, when inserted in a PROFIBUS network, can be accessed through variables. The NJ1001
- %IB(n) BYTE Digital Inputs Byte-0 Input value of channel 00 to 07 Input (Read) Always
- %IB(n+1) BYTE Digital Inputs Byte-1 Input value of channel 10 to 07 Input (Read) Always
- NJ1001 has two variables to access its inputs (Digital Inputs Byte-0 and Digital Inputs Byte-1). Both variables have 8 bits where each bit represents the physical input state of a given input channel. The relationship between each bit and its